Calculate the Dew Point: Calculator, Formula and Table
Calculator and explainer

Table of Contents
The dew point is the temperature air would have to be cooled to before the water vapour it carries starts to condense. Anything colder than that value gets wet. That makes the dew point the decisive number for mould, damp basements and the question of whether ventilating achieves anything at all.
Here you can manually determine whether ventilating is sensible.
Calculating the dew point: the formula
The dew point is derived from two measurements: air temperature T in °C and relative humidity RH in percent. The usual approach is the Magnus formula in the Sonntag (1990) form, which is very accurate between roughly −45 °C and 60 °C.
First compute a helper value γ:
γ = ln(RH / 100) + (17.62 × T) / (243.12 + T)From that the dew point in °C follows:
dew point = (243.12 × γ) / (17.62 − γ)In other words: in a room at 20 °C and 60 % humidity, every surface colder than 12 °C will fog up – an uninsulated corner of an exterior wall, say, or a cold water pipe.
Dew point table
If you would rather not do the maths, read the dew point straight off the table. All values in °C, computed with the same formula as the calculator above:
| Temperature | 40 % | 50 % | 60 % | 70 % | 80 % | 90 % |
|---|---|---|---|---|---|---|
| 0 °C | −12.0 °C | −9.2 °C | −6.8 °C | −4.8 °C | −3.0 °C | −1.4 °C |
| 5 °C | −7.5 °C | −4.6 °C | −2.1 °C | 0.0 °C | 1.8 °C | 3.5 °C |
| 10 °C | −3.0 °C | 0.0 °C | 2.6 °C | 4.8 °C | 6.7 °C | 8.4 °C |
| 15 °C | 1.5 °C | 4.7 °C | 7.3 °C | 9.6 °C | 11.6 °C | 13.4 °C |
| 20 °C | 6.0 °C | 9.3 °C | 12.0 °C | 14.4 °C | 16.4 °C | 18.3 °C |
| 25 °C | 10.5 °C | 13.9 °C | 16.7 °C | 19.1 °C | 21.3 °C | 23.2 °C |
| 30 °C | 14.9 °C | 18.4 °C | 21.4 °C | 23.9 °C | 26.2 °C | 28.2 °C |
Why relative humidity misleads you
The most common mistake when ventilating is comparing relative humidity inside and outside. That does not work, because relative humidity always depends on temperature. Warm air can hold far more water than cold air.
An example that shows the trap:
| Temperature | Relative humidity | Dew point | Absolute humidity | |
|---|---|---|---|---|
| Basement inside | 18 °C | 65 % | 11.3 °C | 10.0 g/m³ |
| Outside air | 25 °C | 60 % | 16.7 °C | 13.8 g/m³ |
The outside air has the lower relative humidity – and still brings almost 4 more grams of water per cubic metre. Ventilating here makes the basement damper, not drier. That is exactly how condensation forms on cold basement walls in summer.
The other way round in winter:
| Temperature | Relative humidity | Dew point | Absolute humidity | |
|---|---|---|---|---|
| Basement inside | 15 °C | 70 % | 9.6 °C | 9.0 g/m³ |
| Outside air | 5 °C | 80 % | 1.8 °C | 5.4 g/m³ |
Here the outside air has the higher relative humidity, yet it carries away 3.6 g/m³ of water. Ventilating pays off.
The rule of thumb
Do not compare relative humidity. Compare absolute humidity in g/m³ – or, as a stand-in, the dew point:
- Outside dew point clearly lower than inside → ventilate. The outside air can absorb moisture.
- Difference below roughly 0.5 g/m³ → save the effort. That is within the measurement tolerance of typical sensors and achieves nothing.
- Outside dew point higher than inside → keep the windows shut. Ventilating would carry extra water in.
The calculator above does this comparison for you and works out both figures: dew point and absolute humidity, inside and outside.
Monitoring the dew point automatically
Doing it by hand works – but only as long as you remember to. It gets interesting when sensors handle the comparison around the clock and switch the fan on and off themselves.
That is exactly what I built with Home Assistant and Node-RED: indoor and outdoor sensors supply temperature and humidity, a flow turns those into absolute humidity, and the fan only runs when the outside air really is drier.
Guide: DIY dew point ventilation with Home AssistantComparability between the two sensors matters more than absolute accuracy. If the same model measures inside and outside, systematic deviations largely cancel out. An error of ±3 % relative humidity corresponds to roughly 0.3–0.5 g/m³ depending on temperature – hence the 0.5 g/m³ dead band before anything switches at all.
Shaded, sheltered from rain and not directly above a sun-baked surface. A sensor in direct sun reports too high a temperature and therefore too low a relative humidity, which makes the calculated absolute humidity systematically wrong.
Frequently asked questions
What is the dew point in simple terms? The temperature at which air can no longer hold its water vapour. Cool it further and the water drops out as condensation.
When does condensation form? As soon as a surface is colder than the dew point of the room air. At 20 °C and 60 %, that means below 12.0 °C.
What is absolute humidity? The actual amount of water in the air, measured in grams per cubic metre. Unlike relative humidity, it can be compared directly between rooms at different temperatures.
Wouldn’t a dehumidifier be simpler? It works regardless of the weather, but it needs constant power, a drain and it makes noise. Dew-point-controlled ventilation uses the outside air instead and only needs power for a fan.